Read through the entire installation section first before beginning installation.
Be very careful when working with batteries. Wear eye protection. Have fresh water available to clean any contact with battery acid.
Use insulated tools and avoid placing metal objects near the batteries.
WARNING: EQUIPMENT DAMAGE OR RISK OF EXPLOSION
Never install the GenStar MPPT in an enclosure with vented/flooded batteries. Battery fumes are flammable and will corrode and destroy the GenStar MPPT circuits.
WARNING: RISK OF FIRE
Over-current protection device interrupt ratings must be a minimum of 2kA, 3kA and 5kA for 12V, 24V, and 48V systems, respectively.
CAUTION: EQUIPMENT DAMAGE
When installing the GenStar MPPT in an enclosure, ensure sufficient ventilation. Installation in a sealed enclosure will lead to over-heating and a decreased product lifetime.
CAUTION: EQUIPMENT DAMAGE
When installing the GenStar MPPT be certain to observe correct polarity when wiring the battery to the controller battery terminals. THERE IS NO REVERSE BATTERY POLARITY PROTECTION.
CAUTION: Equipment Damage
The GenStar MPPT is designed to regulate ONLY solar (photovoltaic) power. Connection to any other type of power source (e.g. wind turbine or generator) may void the warranty. However, other power sources can be connected directly to the battery.
For indoor use only. Do not install in locations where water can enter the controller.
CSA C22.2 #107.1 per Clause 15.4.1.3 requires the installer to apply the additional label on or adjacent to the battery, in a location where it is visible prior to removal of guards, opening of a battery enclosure, etc.
WARNING:
When a ground-fault in indicated, battery terminals and connected circuits may be undergrounded and hazardous.
Be certain that battery terminals and other bare live parts of connected circuits are installed in enclosures or otherwise guarded against inadvertent contact.
Loose power connections and /or corroded wires may result in resistive connections that melt wire insulation, burn surrounding materials, or even cause fire. Ensure tight connections and use cable clamps to secure cables and prevent them from swaying in mobile applications.
Preset charging profiles are designed for lead acid and 4, 8 or 16 cell Lithium LiFePO4 batteries. Custom settings can be used for varied charging requirements (see section 4.2.3 for details). Note that some batteries may not be compatible.
The GenStar MPPT battery connection may be wired to one battery, or a bank of batteries. The following instructions refer to a singular battery, but it is implied that the battery connection can be made to either one battery or a group of batteries in a battery bank.
The GenStar MPPT uses corrosion-resistant fasteners, an anodized aluminum heat sink, and conformal coating to protect it from harsh conditions. However, for long service life, extreme temperatures and marine environments should be avoided.
The GenStar MPPT prevents reverse current leakage at night, so a blocking diode is not required in the system.
The maximum power wire size is 1/0 AWG / 53.5 mm2 (multi-strand). Torque tightly up to 100 in-lb (11.3 Nm).
The maximum equipment grounding terminal wire size is #2 AWG / 33.6 mm2 (multi-strand). Torque tightly up to 50 in-lb / 5.65 Nm.
The maximum load terminal wire size is #6 AWG / 13.3 mm2 (multi-strand). Torque tightly up to 35 in-lb / 3.9 Nm.
Use caution to ensure that all wire strands (especially fine strands) are contained in the terminal lug wire slot. Clamped wire heads are recommended for this purpose.
Verify that the highest temperature compensated solar array open-circuit voltage (Voc) will not exceed 200V, and that load current will not exceed 30 Amps.
Verify that the system battery will maintain voltages between 10-72.
To achieve greater total charging current, multiple controllers can be installed in parallel on the same battery bank.
Each controller in the system must have its own solar array.
The load terminals of multiple GenStar controllers can only be wired together if the total load draw does not exceed 30 Amps.