Wire Sizing Information

Prev Next

Wire sizing requirements are based on the ampacity (current carrying capacity) of conductors. The NEC includes Ampacity Tables which are used to determine the ampacity for a given wire size as indicated in NEC Section 310.15.

GenStar power terminals are rated for 75°C. When wires with a 90°C temperature rating are used with terminals that have a 75°C temperature rating, wire ampacity at 75°C must be used.

Wire ampacity requirements for the battery, PV array and load circuits are:

  • Controller battery wire ampacity must be greater than or equal to 125% of maximum continuous current (battery current rating of the controller)

  • PV array wire ampacity must meet both of the following requirements:

  • Must be greater than or equal to 156% of PV Array Isc without correction and adjustment factors.

  • Must be greater than or equal to 125% of PV Array Isc with correction and adjustment factors.

  • Load wire ampacity must be greater than or equal to the load breaker current rating.

NEC Section 240.4(D) requires a maximum breaker or fuse rating for smaller wire sizes as follows:

  • 14 AWG Copper: 15 Amps OCPD and wire ampacity

  • 12 AWG Copper: 20 Amps OCPD and wire ampacity

  • 10 AWG Copper: 30 Amps OCPD and wire ampacity

Therefore, where load circuit-breakers or fuses are larger than indicated above, a larger wire must be used.

Correction and adjustment factors may also be required to account for the following:

  • Maximum ambient temperature

  • Temperatures at different parts of the circuit (rooftops or engine rooms for example)

  • Wire terminal temperature ratings

  • Multi-conductor cables

  • Conduit fill and other factors