Navigating to Network Settings in Morningstar Mobile App
Network Settings can be found in the Setup Menu as shown below.
.png)
Network Settings page in the mobile app
Navigating to Network Settings in LiveView
NOTE: Installer Access must be enabled and Read-Only Mode (DIP Switch #1) must be Off/Disabled to change network settings.
Network settings can be found in the Setup menu under the Network tab as shown below. The current network settings are summarized on the first card as shown below.
.png)
Network Settings Details
Adjust MODBUS Settings
.png)
Modbus ID - Edit the MODBUS address of the ReadyEdge (default = 1)
Modbus/TCP port - Change the network port for ReadyEdge MODBUS TCP/IP communication (default port = 502)
Bridge Ethernet Modbus/TCP requests to EIA-485 - Switch ON to enable Modbus bridging. When enabled, MODBUS TCP requests received via Ethernet that are NOT addressed to the ReadyEdge ID (default ID = 1) or its connected products will be “bridged” or transmitted serially onto the EIA-485 network to other MODBUS devices. If a device on the EIA-485 network has the correct ID and responds to the message, the ReadyEdge will “bridge” the response from that device back to the Ethernet network with a properly formed MODBUS TCP response message.
NOTE: MODBUS bridging will transmit MODBUS write commands to the EIA-485 network devices even if Read-Only Mode is enabled.
Enable/Disable Morningstar Solar Connect Cloud Service
.png)
Edit TCP IP Network Settings
.png)
Modify Time Servers
If the ReadyEdge is connected to the Internet, it has the ability to periodically synchronize time and date from a time server. There are three pre-populated, public NTP servers, which users can modify as necessary. The ReadyEdge will attempt to connect to Timer Server 1 first to obtain current time and date. If connection fails, it will attempt to connect to Timer Server 2, and so forth.
To enable the use of these time servers, select the “Use Time Servers” option for Date/Time Source under the Date & Time tab.
.png)