MODEL | Wire Size in a raceway, cable, or earth1 | Wire Size in free air2 | Metric Wire Size3 (mm2) | ||
@30°C | 30°-45°C | @30°C | 30°-45°C | ||
GS-MPPT-60 | #4 AWG | 3 AWG > 40°C | #6 AWG | #6 AWG | 16 - 25 |
GS-MPPT-80 | #3 AWG | 2 AWG > 30°C 1 AWG > 40°C | 4 AWG | #.4 AWG | 25 - 35 |
GS-MPPT-100 | #1 AWG | 1/0 > 30°C 2/0 > 40°C | #4 AWG | 3 AWG > 30°C 2 AWG > 40°C | 35 - 50 |
1 Per NEC 2021 [see NEC Table 310.15(b)(16)], ampacity for not more than three current-carrying conductors in a raceway, cable, or earth (buried)
2 Per NEC 2021 [see NEC Table 310.15(b)(17)], ampacity for conductors in free air
3 Estimated. See local code requirements for metric cable sizing
Table A-2. Minimum DC battery wire sizes for 75ºC copper.