Voltage Drop Chart for 75°C or 90ºC Stranded Copper Wire

Prev Next

Maximum 1-way distance (feet), 12 Volt system - multiply values by (2) for 24 Volt, and by (4) for 48V, system

Wire Size (AWG)

100A

90A

80A

70A

60A

55A

50A

45A

40A

35A

30A

25A

20A

15A

4/01

23.5

26.1

294

33.6

39.2

.42.8

47.0

52.3

58.8

67.2

78.4

94.1

117.6

156.8

3/01

18.7

20.7

23.3

26.7

31.1

33.9

37.3

41.5

46.7

53.3

62.2

74.7

93.3

12.4.5

2/01

14.8

16.4

18.5

21.1

24.6

26.9

29.6

32.9

37.0

42.3

49.3

59.2

73.9

98.6

1/0

11.7

13.0

14.7

16.7

19.5

21.3

23.4

26.0

29.3

33.5

39.1

46.9

58.6

78.1

#1

9.3

10.3

11.6

13.3

15.5

16.9

18.6

20.6

23.2

26.5

31.0

37.1

46.4

61.9

#2

7.4

8.2

9.2

10.5

12.3

13.4

14.7

16.4

18.4

21.1

24.6

29.5

36.9

49.1

#3

5.8

6.5

7.3

8.3

9.7

10.6

11.7

13.0

14.6

16.7

19.5

23.3

29.2

38.9

#.4

4.6

5.2

5.8

6.6

7.7

8.4

9.3

10.3

11.6

13.3

15.5

18.6

23.2

31.0

#6

3.6

4.2

4.9

5.3

5.8

6.5

7.3

8.3

9.7

11.6

14.6

19.4

#8

3.1

3.3

3.7

4.1

4.6

5.3

6.1

7.4

9.2

12.3

#10

2.9

3.3

3.8

.4.6

5.8

7.7

#12

2.9

3.6

4.8

#14

2.3

3.0

1 Wires sizes larger than 1/0 AWG must be terminated at a splicer block located external to the GenStar MPPT. Use 1/0 AWG or smaller wire to connect to the GenStar MPPT to the splicer block.

Table A-4. Maximum 1-way wire distance for 12 Volt systems, stranded copper, 2% voltage drop

Maximum 1-way distance (meters), 12 Volt system - multiply values by (2) for 24 Volt, and by (4) for 48V, system

Wire Size (mm2)

100A

90A

80A

70A

60A

55A

50A

45A

40A

35A

30A

25A

20A

15A

1201

7.6

8.5

9.6

10.9

12.7

13.9

15.3

17.0

19.1

21.8

25.5

30.6

38.2

51.0

951

6.1

6.7

7.6

8.7

10.1

11.0

12.1

13.5

15.2

17.4

20.2

24.3

30.4

40.5

701

4.4

4.9

5.5

6.3

7.3

8.0

8.8

9.8

11.0

12.6

14.7

17.6

22.0

294

50

3.1

3.4

3.8

4.4

5.1

5.5

6.1

6.8

7.6

8.7

10.2

12.2

15.3

20.3

35

2.3

2.5

2.8

3.2

3.8

4.1

4.5

5.0

5.6

6.4

7.5

9.0

11.3

15.0

25

1.6

1.8

2.0

2.3

2.7

3.0

3.3

3.6

4.1

4.6

5.4

6.5

8.1

10.8

16

1.5

1.7

1.9

2.1

2.3

2.6

2.9

3.4

4.1

5.2

6.9

10

1.3

1.4

1.6

1.8

2.2

2.6

3.2

4.3

6

1.3

1.5

1.9

2.6

.4

1.0

1.3

1.7

2.5

0.8

1.1

1 Wires sizes larger than 50 mm2 must be terminated at a splicer block located external to the GenStar MPPT. Use 50 mm2 or smaller wire to connect to the GenStar MPPT to the splicer block.

Table A-5. Maximum 1-way wire distance for 12 Volt systems, stranded copper, 2% voltage drop.