NOTE: DEFINITION
Overcurrent protection devices are defined as breakers or fuses. Strictly, a disconnect switch is device that only breaks a circuit, but provides no overcurrent protection.
WARNING: SHOCK AND FIRE HAZARDS
Installation must comply with all U.S. National Electrical Code, Canadian Electrical Code or local code requirements.
WARNING: SHOCK AND FIRE HAZARDS
Solar, load, and battery overcurrent protection are required in the system. These protection devices are external to the GenStar MPPT controller, and must be sized as required by the NEC or local code requirements.
WARNING: SHOCK AND FIRE HAZARDS
Circut Breakers or fused disconnect switches can serve as a means of disconnection, and should be at a readily accessible location. For best practices and safety guidance, see NEC 690 ,"Part III - Disconnecting Means", for disconnect requirements for PV systems, in addition to other code requirements.
WARNING: SHOCK AND FIRE HAZARDS
Fuses, single-pole circuit breakers, or single-pole disconnect switches must only be installed on ungrounded system conductors. The NEC allows and may require the use of double-pole breakers or double-pole disconnect switches which break both the grounded and ungrounded conductors of the PV array or load conductors.
WARNING: SHOCK AND FIRE HAZARDS
When using a disconnect switch, install a fuse or breaker in series to provide overcurrent protection.
CAUTION:
All breakers, fuses and disconnect switches must be rated for the maximum voltage of the circuit or higher. These devices are external to the GenStar MPPT controller.
BATTERY OVER-CURRENT PROTECTION DEVICE SIZING
The U.S. NEC requires the installation of DC breakers or fused disconnect switches in all battery circuits in order to provide both a means of disconnection and overcurrent protection.
The battery breaker or fused disconnect switch(es) should be located near the battery or the battery busbar. Where the controller battery terminals are more than 1.5m (5 feet) from the battery, or where circuits from these terminals pass through a wall or partition, U.S. NEC requires that a means of disconnection be provided at the battery and solar controller with overcurrent protection at the DC (battery) power source.
The minimum battery disconnect switch current rating is the current rating of the controller being installed. To provide over-current protection when using a disconnect switch, a properly sized fuse or breaker must be installed in series.
Battery breakers or fuses must be sized with a minimum of 125% of the continuous output current rating of the solar controller. Recommended battery circuit fuse or breaker current ratings:
MODEL | Battery Circuit Breaker/Fuse Rating |
GS-MPPT-60M-200V | 75 or 80 Amps |
GS-MPPT-80M-200V | 100 Amps |
GS-MPPT-100M-200V | 125 Amps |
Table 1. Battery Circuit Breaker/Fuse Current Ratings Meeting U.S. National Electrical Code.
PV Input Over-Current Protection Device (OCPD) And Disconnect Switch Ratings
WARNING: SHOCK AND FIRE HAZARDS
The solar array open-circuit voltage (Voc) at the worst-case (coldest) module temperature must not exceed the PV disconnect or overcurrent protection voltage ratings.
As defined in NEC Section 690.9, PV input disconnect switches must have a current rating greater than or equal to the maximum PV array current (Isc) multiplied 1.25 PV array Isc = # of strings multiplied by the module Isc (STC) rating.
Note that individual PV string circuits do not require disconnects.
NEC Section 690.9 provides requirements for overcurrent protection. These requirements are based on the maximum PV array current which equals 1.25 multiplied by array Isc, as defined in NEC Section 690.9.
The PV input breaker or fuse rating should not be less than the next higher breaker rating above 156% of the PV array Isc. Maximum PV breaker or fuse ratings are:
MODEL | Maximum PV Breaker or fuse Rating |
GS-MPPT-60M-200V | 80 Amps |
GS-MPPT-80M-200V | 100 Amps |
GS-MPPT-100M-200V | 125 Amps |
Table 2. PV Input Circuit Maximum Breaker or Fuse Current Ratings.
String breakers or fuses are also required for parallel strings and are typically included with the PV string combiner. There may be other code requirements specific to the installation of a particular PV array.
As allowed for in NEC Section 690.9(A), PV input overcurrent protection is not required if both of the following conditions are met:
PV wire ampacity is sufficient to carry the maximum PV array current (ampacity is greater than 156% of PV array Isc).
The maximum PV array current (125% of PV array Isc) is less than the maximum input Isc current rating of the controller and PV disconnect rating.
If 156% of PV array Isc is greater than the maximum PV input breaker or fuse current rating, the PV array breaker or fuse should be located at the output of the PV array combiner.
Load Output Overcurrent Protection Devices (OCPD) and Disconnect Switches
The output/load breaker or fuse rating must be no greater than 40 Amps.
The load fuse or breaker must be sized at a minimum of 125% of the maximum load output current. The maximum load output current is the sum of the branch load circuits or the controller load output current rating.
The load/output breaker or fused disconnect switch should be located near the load output terminals of the controller.
The load output disconnect switch must have a minimum current rating greater than or equal to the fuse current rating, but is not required to be higher than the load output current rating of the controller.