4.3 Load Control Information

Prev Next

The primary purpose of the load control function is to disconnect system loads when the battery has discharged to a low state of charge, and to reconnect system loads when the battery is sufficiently recharged. System loads may be lights, DC appliances, or other electronic devices. The total current draw of all loads must not exceed the GenStar 30 Amp maximum load rating.

Low Voltage Disconnect/Reconnect Profiles

GenStar MPPT offers seven (7) Low Voltage Disconnect/Reconnect (LVD/LVR) Profiles for load control, as seen in Tables 9 below. This includes current compensation (mV/A) values. All voltage and mV/A settings listed are for nominal 12 Volt batteries. Multiply the voltage settings by two (2) or (.4), for 24 and 48 Volt systems, respectively.

GenStar MPPT Low Voltage Disconnect/Reconnect (LVD-LVR) Profiles

Load Control Type- Preset

LVD

LVR

LVD Warning

Current Comp.

Volts

Volts

Minutes

mV/A

1 - Lead Acid

11.10

12.60

10

0

2 - Lead Acid

11.50

12.80

10

-4

3 - Lead Acid

11.70

12.90

20

-6

4 - Lead Acid

12.00

13.20

20

-6

5 - Lithium LiFePO4

12.50

13.15

1

0

6 - Lithium LiFePO4

12.70

13.25

2

-1

7 - Lithium LiFePO4

12.85

13.30

5

-2

Table 9. GenStar MPPT Preset LVD-LVR (Load Control) Profiles.

Current Compensation

Each load control profile specifies its own current compensation - some being zero. Under load, the battery voltage will sag in proportion to the current draw of the load. Without a current compensation feature, a short-term large load could cause a premature LVD. Current Compensation settings are inversely proportional to the battery bank amp hours. Therefore, it is important not to set the Current Compensation too high for larger battery banks.

LVD Warning/LVD/LSoCD Warning Time

As the battery discharges, the Battery SOC LEDs will transition from green to yellow and then from yellow to flashing red. The LEDs flash red when the battery voltage is < LVD or SOC < LSOCD set-point. If the battery voltage remains below the LVD or LSOCD set-point for longer than the LVD Warning time, the load will disconnect and a solid red Battery SOC LED indication will be displayed.

The amount of time between a green SOC indication and load disconnect will depend on many factors including:

  • Rate of discharge (amount of load draw)

  • Capacity of the battery

  • Health of the battery

  • LVD set-point

Load HVD/HVR

Load HVD/HVR is disabled for all lead-acid load control profiles (1-4). Load HVD is not temperature compensated and therefore, should only be used with lead acid batteries if HVD is higher than the maximum temperature compensated regulation voltage or Maximum Regulation Voltage setpoint. Load HVD/HVR is 14.8V / 13.7V for all of the LiFePO4 load control profiles (6 - 8).