Factory Reset must be done using the on-board meter display. Navigate to Setup\Advanced Setup\Installer Setup, and enter Installer Password. If no password is set in memory (factory default), then LiveView will prompt you to create one. Then navigate to Commands\Factory Reset and choose that option. After a factory reset, the unit will need to be re-commissioned.
NOTE:
The GenStar MPPT does not use universal default passwords and requires unique credentials to be created on first use. LiveView will prompt for an Administrative password the first time the webpage is loaded. The Lock/Unlock buttons will not be visible until a password is established.
NOTE: RESTORING SETTINGS AFTER A FACTORY RESET
If you wish to restore the settings after a factory reset, make sure the settings have been saved to the internal SD card before performing the factory reset. Settings can be saved with the meter display or with LiveView. When saving the settings a system image is created. The system image is a copy of ALL of the settings, including the commissioning settings. The complete system image configuration can then be quickly loaded after recommissioning.
WARNING: RISK OF EXPLOSION
When loading a system image configuration from an SD Card, ensure that the destination device has been commissioned for the same system voltage, battery profile, and RTS; otherwise, there is a potential risk of system damage or bodily injury.