WARNING: Shock Hazard
DO NOT CONNECT LIVE AC WIRING. ENSURE AC POWER IS DISCONNECTED AT THE SOURCE. VERIFY AC POWER IS DISCONNECTED WITH A MULTIMETER BEFORE PROCEEDING WITH THESE INSTRUCTIONS.
AVERTISSEMENT : Risque de choc électrique
NE PAS CONNECTER DE CÂBLAGE CA SOUS TENSION. ASSUREZ-VOUS QUE L'ALIMENTATION CA EST DÉCONNECTÉE À LA SOURCE. VÉRIFIEZ QUE L'ALIMENTATION CA EST DÉCONNECTÉE AVEC UN MULTIMÈTRE AVANT DE SUIVRE CES INSTRUCTIONS.
.png)
AC Detect Terminal
The AC Detect Function is designed to detect whether AC voltage is present on the connected circuit or not. This feature reports a simple Yes/No value in LiveView and other user interfaces. It does not report a precise voltage or frequency measurement, but instead determines if the AC source is in a valid range according to the following criteria:
AC Voltage between ~40 Vac to 300 Vac
AC Frequency > 30 Hz
Use this feature for the following:
Monitor the presence of AC voltage from a generator, grid or inverter.
Confirm that the generator start command successfully started the system generator.
Detect the presence or absence of AC grid or inverter AC voltage, then take certain actions
Turn on and off Relays with the ReadyRelay (typically for loads) when AC voltage is detected.
The AC Detect Port can accept up to 240 Vac RMS (300 Vac peak) and uses spring clamps for wiring.
Wiring Instructions
WARNING: Fire Hazard
WHEN CONNECTING THE AC DETECT WIRES, INSTALL A 5 AMP FUSE IN THE UNGROUNDED AC WIRE, WITHIN SIX INCHES (150 MM) OF THE AC SOURCE TERMINAL CONNECTION.
AVERTISSEMENT : Risque d'incendie
LORS DE LA CONNEXION DES FILS DE DÉTECTION CA, INSTALLEZ UN FUSIBLE DE 5 AMPÈRES DANS LE FIL CA NON MIS À LA TERRE, À MOINS DE SIX POUCES (150 MM) DE LA BORNE DE CONNEXION DE LA SOURCE CA.
Connect the Neutral and Line AC wires from the AC power circuit to the corresponding connections on the AC Detect terminal block according to the markings on the product.
Ensure a sufficient amount of insulation has been stripped from the wires and the spring termination has securely clamped the wiring conductors.